Initial Window Operation
Testing Procedures
Action Reaction
Turn the power “OFF” at the rocker switch
located on the controller unit.
Manually open and close the door several times.
When the door is opening, the “MOTOR RUN”
lamp will illuminate green. When the door is
closing, “MOTOR RUN” lamp will illuminate red.
The “POWER” lamp must illuminate during both
operations. If neither of these lamps illuminate
during any of the processes, proceed to the
“Troubleshooting” section.
Turn the power “ON” at the rocker switch located
on the controller unit.
Break the electric eye beam to open the door.
The door will open.
With the power “ON” break the electric eye beam
momentarily to open and close the door.
The door will open. They will remain in the open
position for either approximately 3.0 or 6.0
seconds before closing (Default Settings)
With the power “ON” press the “CLOSE DELAY”
button located on the controller unit once and
break the electric eye beam to open the door
The door will open and the length of time that the
door remains open will toggle between 3.0 and
6.0 seconds before closing. (Default Settings)
With the power “ON” break the electric eye beam
momentarily to open and close the door. Insert an
object at least 4” (101.6mm) wide between the
door and the frame as the door closes.
The door will automatically reverse their action
(the door will open), when an object is caught
between or restricting the closing of the door.